| 1 | +# Database for MPC ion pump controller using Gamma Protocol for Ethernet |
| 2 | +# Serial uses a different protocol |
| 3 | +# |
| 4 | +# Parameters |
| 5 | +# $(P) PV name prefix (e.g. 13IDA:) |
| 6 | +# $(PUMP) PV name for this specific ion pump (e.g. ip1:) |
| 7 | +# $(PORT) asyn PORT name |
| 8 | +# $(PN) Pump number (1 or 2) |
| 9 | + |
| 10 | +record(stringin,"$(P)$(PUMP):STAT") { |
| 11 | + field(SCAN, "1 second") |
| 12 | + field(DTYP, "stream") |
| 13 | + field(INP, "@MPC_Ethernet.proto readString(OD,$(PN)) $(PORT)") |
| 14 | + field(FLNK, "$(P)$(PUMP):PRES PP MS") |
| 15 | +} |
| 16 | + |
| 17 | +record(ai,"$(P)$(PUMP):PRES") { |
| 18 | + field(PREC, "1") |
| 19 | + field(DTYP, "stream") |
| 20 | + field(INP, "@MPC_Ethernet.proto readFloat(OB,$(PN)) $(PORT)") |
| 21 | + field(FLNK, "$(P)$(PUMP):CUR PP MS") |
| 22 | +} |
| 23 | + |
| 24 | +record(ai,"$(P)$(PUMP):CUR") { |
| 25 | + field(PREC, "1") |
| 26 | + field(DTYP, "stream") |
| 27 | + field(INP, "@MPC_Ethernet.proto readFloat(OA,$(PN)) $(PORT)") |
| 28 | + field(FLNK, "$(P)$(PUMP):VOLT PP MS") |
| 29 | +} |
| 30 | + |
| 31 | +record(ai,"$(P)$(PUMP):VOLT") { |
| 32 | + field(PREC,"0") |
| 33 | + field(DTYP, "stream") |
| 34 | + field(INP, "@MPC_Ethernet.proto readFloat(OC,$(PN)) $(PORT)") |
| 35 | +} |
| 36 | + |
| 37 | +record(ai,"$(P)$(PUMP):SIZE") { |
| 38 | + field(SCAN, "5 second") |
| 39 | + field(PREC, "0") |
| 40 | + field(DTYP, "stream") |
| 41 | + field(INP, "@MPC_Ethernet.proto readInt(11,$(PN)) $(PORT)") |
| 42 | +# field(FLNK,"$(P)$(PUMP):SP1V PP MS") |
| 43 | + field(FLNK,"$(P)$(PUMP):GAUTOS PP MS") |
| 44 | +} |
| 45 | + |
| 46 | +# Setpoints are not currently implemented. |
| 47 | +# The MPCq has a different syntax from the MPC, and we are not currently using them. |
| 48 | +record(ai,"$(P)$(PUMP):SP1V") { |
| 49 | + field(DTYP, "stream") |
| 50 | + field(PREC,"1") |
| 51 | + field(INP, "@MPC_Ethernet.proto readFloat(OC,$(PN)) $(PORT)") |
| 52 | + field(FLNK,"$(P)$(PUMP):SP1S PP MS") |
| 53 | +} |
| 54 | + |
| 55 | +record(bi,"$(P)$(PUMP):SP1S") { |
| 56 | + field(DTYP, "stream") |
| 57 | + field(INP, "@MPC_Ethernet.proto readInt(OC,$(PN)) $(PORT)") |
| 58 | + field(ZSV,"MAJOR") |
| 59 | + field(ZNAM,"Off") |
| 60 | + field(ONAM,"On") |
| 61 | + field(FLNK,"$(P)$(PUMP):SP2V PP MS") |
| 62 | +} |
| 63 | + |
| 64 | +record(ai,"$(P)$(PUMP):SP2V") { |
| 65 | + field(DTYP, "stream") |
| 66 | + field(PREC,"1") |
| 67 | + field(INP, "@MPC_Ethernet.proto readFloat(OC,$(PN)) $(PORT)") |
| 68 | + field(FLNK,"$(P)$(PUMP):SP2S PP MS") |
| 69 | +} |
| 70 | + |
| 71 | +record(bi,"$(P)$(PUMP):SP2S") { |
| 72 | + field(DTYP, "stream") |
| 73 | + field(INP, "@MPC_Ethernet.proto readInt(OC,$(PN)) $(PORT)") |
| 74 | + field(ZSV,"MAJOR") |
| 75 | + field(ZNAM,"Off") |
| 76 | + field(ONAM,"On") |
| 77 | + field(FLNK,"$(P)$(PUMP):SP3V PP MS") |
| 78 | +} |
| 79 | + |
| 80 | +record(ai,"$(P)$(PUMP):SP3V") { |
| 81 | + field(DTYP, "stream") |
| 82 | + field(PREC,"1") |
| 83 | + field(INP, "@MPC_Ethernet.proto readFloat(OC,$(PN)) $(PORT)") |
| 84 | + field(FLNK,"$(P)$(PUMP):SP3S PP MS") |
| 85 | +} |
| 86 | + |
| 87 | +record(bi,"$(P)$(PUMP):SP3S") { |
| 88 | + field(DTYP, "stream") |
| 89 | + field(INP, "@MPC_Ethernet.proto readInt(OC,$(PN)) $(PORT)") |
| 90 | + field(ZSV,"MAJOR") |
| 91 | + field(ZNAM,"Off") |
| 92 | + field(ONAM,"On") |
| 93 | + field(FLNK,"$(P)$(PUMP):SP4V PP MS") |
| 94 | +} |
| 95 | + |
| 96 | +record(ai,"$(P)$(PUMP):SP4V") { |
| 97 | + field(DTYP, "stream") |
| 98 | + field(PREC,"1") |
| 99 | + field(INP, "@MPC_Ethernet.proto readFloat(OC,$(PN)) $(PORT)") |
| 100 | + field(FLNK,"$(P)$(PUMP):SP4S PP MS") |
| 101 | +} |
| 102 | + |
| 103 | +record(bi,"$(P)$(PUMP):SP4S") { |
| 104 | + field(DTYP, "stream") |
| 105 | + field(INP, "@MPC_Ethernet.proto readInt(OC,$(PN)) $(PORT)") |
| 106 | + field(ZSV,"MAJOR") |
| 107 | + field(ZNAM,"Off") |
| 108 | + field(ONAM,"On") |
| 109 | + field(FLNK,"$(P)$(PUMP):GAUTOS PP MS") |
| 110 | +} |
| 111 | + |
| 112 | +record(bi,"$(P)$(PUMP):GAUTOS") { |
| 113 | + field(DTYP, "stream") |
| 114 | + field(INP, "@MPC_Ethernet.proto readAutoRestart($(PN)) $(PORT)") |
| 115 | + field(OSV, "MAJOR") |
| 116 | + field(ZNAM, "No") |
| 117 | + field(ONAM, "Yes") |
| 118 | +} |
| 119 | + |
| 120 | +# The MPCq does not support this command since all values are displayed |
| 121 | +# Retain the record so the OPI screens are not white |
| 122 | +record(mbbo,"$(P)$(PUMP):DIS") { |
| 123 | +# field(DTYP, "stream") |
| 124 | +# field(OUT, "@MPC_Ethernet.proto setString(25,$(PN)) $(PORT)") |
| 125 | + field(ZRVL,"0") |
| 126 | + field(ONVL,"1") |
| 127 | + field(TWVL,"2") |
| 128 | + field(ZRST,"Pressure") |
| 129 | + field(ONST,"Current") |
| 130 | + field(TWST,"Voltage") |
| 131 | +} |
| 132 | + |
| 133 | +record(ao,"$(P)$(PUMP):SSIZE") { |
| 134 | + field(DTYP, "stream") |
| 135 | + field(OMSL, "supervisory") |
| 136 | + field(PREC, "0") |
| 137 | + field(OUT, "@MPC_Ethernet.proto writeInt(12,$(PN)) $(PORT)") |
| 138 | + field(VAL, "30") |
| 139 | +} |
| 140 | + |
| 141 | +# Setpoints are not currently implemented. |
| 142 | +# The MPCq has a different syntax from the MPC, and we are not currently using them. |
| 143 | +record(ao,"$(P)$(PUMP):SET1") { |
| 144 | + field(DTYP, "stream") |
| 145 | + field(OMSL, "supervisory") |
| 146 | + field(PREC, "1") |
| 147 | + field(OUT, "@MPC_Ethernet.proto writeFloat(25,$(PN)) $(PORT)") |
| 148 | + field(VAL, "1.0E-06") |
| 149 | +} |
| 150 | + |
| 151 | +record(ao,"$(P)$(PUMP):SET2") { |
| 152 | + field(DTYP, "stream") |
| 153 | + field(OMSL, "supervisory") |
| 154 | + field(PREC, "1") |
| 155 | + field(OUT, "@MPC_Ethernet.proto writeFloat(25,$(PN)) $(PORT)") |
| 156 | + field(VAL, "1.0E-06") |
| 157 | +} |
| 158 | + |
| 159 | +record(ao,"$(P)$(PUMP):SET3") { |
| 160 | + field(DTYP, "stream") |
| 161 | + field(OMSL, "supervisory") |
| 162 | + field(PREC, "1") |
| 163 | + field(OUT, "@MPC_Ethernet.proto writeFloat(25,$(PN)) $(PORT)") |
| 164 | + field(VAL, "1.0E-06") |
| 165 | +} |
| 166 | + |
| 167 | +record(ao,"$(P)$(PUMP):SET4") { |
| 168 | + field(DTYP, "stream") |
| 169 | + field(OMSL, "supervisory") |
| 170 | + field(PREC, "1") |
| 171 | + field(OUT, "@MPC_Ethernet.proto writeFloat(25,$(PN)) $(PORT)") |
| 172 | + field(VAL, "1.0E-06") |
| 173 | +} |
| 174 | + |
| 175 | +record(bo,"$(P)$(PUMP):STOP") { |
| 176 | + field(DTYP, "stream") |
| 177 | + field(OUT, "@MPC_Ethernet.proto writeHVOnOff($(PN)) $(PORT)") |
| 178 | + field(OSV, "MAJOR") |
| 179 | + field(ZNAM, "START") |
| 180 | + field(ONAM, "STOP") |
| 181 | +} |
| 182 | + |
| 183 | +# This function is not supported on the MPCq, keep the record for OPI displays |
| 184 | +record(bo,"$(P)$(PUMP):ULCK") { |
| 185 | +# field(DTYP, "stream") |
| 186 | +# field(OUT, "@MPC_Ethernet.proto writeString(25,$(PN)) $(PORT)") |
| 187 | + field(OSV, "MAJOR") |
| 188 | + field(ZNAM, "LOCK") |
| 189 | + field(ONAM, "UNLOCK") |
| 190 | +} |
| 191 | + |
| 192 | +record(bo,"$(P)$(PUMP):SAUTOS") { |
| 193 | + field(DTYP, "stream") |
| 194 | + field(OUT, "@MPC_Ethernet.proto writeAutoRestart($(PN)) $(PORT)") |
| 195 | + field(OSV, "MAJOR") |
| 196 | + field(ZNAM, "No") |
| 197 | + field(ONAM, "Yes") |
| 198 | +} |
0 commit comments